If the ambient temperature is 40°C:

Derating factor = 0.87 CCC = 18.5 A × 0.87 = 16.1 A

The specific values for current-carrying capacity are found in , specifically in Table B.52.12 (for copper conductors, PVC insulation).

Iec 60364 Current Carrying Capacity 1.5 Mm2 !full! 🔥

If the ambient temperature is 40°C:

Derating factor = 0.87 CCC = 18.5 A × 0.87 = 16.1 A iec 60364 current carrying capacity 1.5 mm2

The specific values for current-carrying capacity are found in , specifically in Table B.52.12 (for copper conductors, PVC insulation). If the ambient temperature is 40°C: Derating factor = 0